The Centralized Emergency Lighting Bypass differentiates between emergency and normal operation mode by monitoring power. During normal operation, the inspeXtor server is online and emergency light fixture is driven by a LED node driver which powers and controls the fixture using PoE InspeXtor. In the event of power failure (Emergency Mode),the inspeXtor server is offline, controls are disable and AutomaticTransfer Switch (ATS) will activate the emergency power circuit and powered onboard specified emergency light fixture for maximum brightness. When normal power is restored, the inspeXtor server is online and Automatic Transfer Switch (ATS) back to PoE operation mode as soon as power is available.
Operation Test Procedure
During normal operation, the inspeXtor server is online and emergency light fixture is driven by a LED node driver which powers and controls the fixture using PoE InspeXtor.
- Verify all lights illuminated up to maximum brightness.
- Verify all control are enable by pressing wall switch or remote control for inspeXtor.
Emergency Operation Test Procedure
Pressing the emergency TEST button on InspeXtor simulates a power failure and forces the system into the Emergency Mode. During emergency mode only the specified emergency light fixture illuminated up to maximumbrightness. Basically the emergency test condition will force the light fixture to use emergency power source during the power failure.
- Go to InspeXtor and press TEST button to start emergency test mode.
- Verify all specified emergency lights illuminated up to maximum brightness.
- Verify controls are disable by pressing wall switch.
- Again press TEST button to EXIT emergency test mode and run system on normal operation.
- Verify all control are enable by pressing wall switch or remote control for inspeXtor